close print view
Radiographic or Radiographic-Fluoroscopic Shielding Guidelines
| |
High Workload
(e.g., rooms in hospitals and in radiology and orthopedic offices) |
Moderate Workload
(e.g., rooms in medical and chiropractic offices) |
Low Workload
(e.g., rooms in podiatry and veterinary offices) |
| |
Up to 1000 mA-min/week |
Up to 250 mA-min/week |
Up to 15 mA-min/week |
| |
Lead
(inches) |
Concrete
(inches) |
Lead
(inches) |
Concrete
(inches) |
Lead
(inches) |
Concrete
(inches) |
| Operator Shields |
1/16 |
5 |
1/16 |
5 |
1/16 |
5 |
| |
|
|
|
|
|
|
| Primary Beams |
|
|
|
|
|
|
| Walls |
3/32 - 1/8 |
6 - 7 |
1/16 - 1/8 |
3 - 6 |
1/16 |
3 |
| Floors |
3/32 - 1/8 |
6 - 8 |
1/16 - 3/32 |
4 - 6 |
1/16 |
4 |
| |
|
|
|
|
|
|
| Secondary Radiation |
|
|
|
|
|
|
| Walls |
1/16 |
3 - 4 |
1/32 - 1/16 |
3 |
0 - 1/32 |
1 |
| Doors |
1/16 |
------- |
1/32 - 1/16 |
------- |
0 - 1/32 |
------- |
| Floors |
1/32 - 1/16 |
2.5 - 3.5 |
1/32 |
2.5 |
0 - 1/32 |
1 |
| Ceilings |
1/32 - 1/16 |
2.5 - 3.5 |
1/32 |
2.5 |
0 - 1/32 |
1 |
updated February 14, 2005
The above concrete thicknesses are based on the use of standard-density concrete with a density of 147 pounds per cubic foot.
Additional shielding design guidance
Related Documents> BHCS/HFS-852; Application for a Radiation Shielding Plan Review - 508021 bytes
|